Character
1) Intake air filter, silica gel desiccant wheel, double cold-water heat exchanger;
2) Chain drive;
3) Electric heating by stainless steel tube, or by copper tube aluminum fin;
4) Efficient centrifugal fans, aluminum alloy frame, high pressure polyurethane and double foam layer cabinet, anti-cold bridge, electric multi-protection operation;
5) Reliable PLC control system.
Model Example
ZLB-D-1000
ZLB: low humidity dehumidifier units basic code
D: Rotary regeneration type. D for Electricity, Z for Steam.
1000: Process airflow m3/h
Main Parameters
Main Parameters / Model
|
ZLB-Z-780000
|
Process Air
|
Airflow m³/h
|
78000
|
|
Fan Power kW
|
55+55
|
Regeneration Air
|
Airflow m³/h
|
26000
|
|
Fan Power kW
|
15.0
|
Steam Consumption
|
For regeneration kg/h
|
800
|
|
Additional heating kg/h
|
207
|
Cooling Capacity
|
Deep well water kW
|
715
|
|
Chilled water kW
|
1160
|
Water Consumption
|
Deep well water t/h
|
123
|
|
Chilled water t/h
|
200
|
Drive Motor Power kW
|
0.2
|
Installed Power
|
Electrical Heating kW
|
/
|
|
Steam Heating kW
|
125.2
|
Overall Dimensions
|
Length mm
|
14000
|
|
Width mm
|
4200
|
|
Height mm
|
4560
|
Weight kg
|
6000
|
Note:
1. Parameter of fresh air: 35°C, 80%2. The ratio of fresh air is 5% of air output.3. Output air excess pressure ≥200Pa4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one.