Character
1.Consist
|
Consist of the fresh air filter, fresh air surface cooler, return air filter, former surface cooler,
and super silicone rotor section, tempering section and regeneration parts.
|
2.Regeneration
|
Regeneration heating by stainless steel tube electric heater or by copper tube aluminum fin steam heater.
|
3.Structure
|
Efficient centrifugal fans, high-strength structural framework, high-pressure foam double-sided enclosure, anti-cold bridge treatment.
|
4.Control
|
PLC control, electric multi-protection, operation safety, stable and reliable.
|
Model Example
ZLB-D-1000
ZLB: low humidity dehumidifier units basic code
D: Rotary regeneration type. D for Electricity, Z for Steam.
1000: Process airflow m3/h
Main Parameters of ZLB Series Low Humidity Dehumidifier
Main Parameters / Model
|
ZLB-1000
|
ZLB-5000
|
ZLB-10000
|
Process Air
|
Airflow m³/h
|
1000
|
5000
|
10000
|
Fan Power kW
|
1.1
|
4.0
|
7.5
|
Regeneration Air
|
Airflow m³/h
|
340
|
1650
|
3450
|
Fan Power kW
|
0.25
|
1.5
|
3.0
|
Regeneration Mode
|
Electrical Heating Power kW
|
8.4
|
36
|
84
|
Steam Consumption kg/h
|
14
|
60
|
140
|
Outlet Air
|
Temperature °C
|
22±2
|
Relative Humidity %
|
≤20
|
Drive Motor Power kW
|
0.06
|
0.12
|
0.16
|
Installed Power
|
Electrical Heating kW
|
9.81
|
41.62
|
94.68
|
Steam Heating kW
|
1.41
|
5.62
|
10.68
|
Overall Dimensions
|
Length mm
|
5000
|
5700
|
6000
|
Width mm
|
800
|
1230
|
1630
|
Height mm
|
1800
|
2300
|
2650
|
Weight kg
|
1200
|
1800
|
2400
|
Supporting System Refrigerating Capacity kW
|
10.0
|
49.9
|
99.8
|
Frozen Water Consumption t/h
|
1.7
|
8.6
|
17.2
|
Note:
1. Parameter of fresh air: 35°C, 80%
2. The ratio of fresh air is 5% of air output.
3. Output air excess pressure ≥200Pa
4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one.
Main Accessories