Superior Quality Low Humidity Dehumidifier Units
Place of Origin Zhejiang, China (Mainland)
Brand Name Peritek
Model Number ZLB Series
Color Blue/White
 Character

1.Consist

Consist of the fresh air filter, fresh air surface cooler, return air filter, former surface cooler,

and super silicone rotor section, tempering section and regeneration parts.

2.Regeneration

Regeneration heating by stainless steel tube electric heater or by copper tube aluminum fin steam heater.

3.Structure

Efficient centrifugal fans, high-strength structural framework, high-pressure foam double-sided enclosure, anti-cold bridge treatment.

4.Control

PLC control, electric multi-protection, operation safety, stable and reliable.

 

 

Model Example

ZLB-D-1000

ZLB: low humidity dehumidifier units basic code 

D: Rotary regeneration type. D for Electricity, Z for Steam.

1000: Process airflow m3/h

 

Main Parameters of ZLB Series Low Humidity Dehumidifier

 

Main Parameters /  Model 

ZLB-1000

ZLB-5000

ZLB-10000

Process Air

Airflow m³/h

1000

 5000

10000

Fan Power kW

1.1

4.0

7.5

Regeneration Air

Airflow m³/h

340

1650

3450

Fan Power kW

0.25

1.5

3.0

Regeneration Mode

Electrical Heating Power kW

8.4

36

84

Steam Consumption kg/h

14

60

140

Outlet Air

Temperature °C

22±2

Relative Humidity %

≤20

Drive Motor Power kW

0.06

0.12

0.16

Installed Power

Electrical Heating  kW

9.81

41.62

94.68

Steam Heating kW

1.41

5.62

10.68

Overall Dimensions

Length  mm

5000

5700

6000

Width  mm

800

1230

1630

Height  mm

1800

2300

2650

Weight kg

1200

1800

2400

Supporting System Refrigerating Capacity kW

10.0

49.9

99.8

Frozen Water Consumption t/h

1.7

8.6

17.2

 

Note:

1. Parameter of fresh air: 35°C, 80%

2. The ratio of fresh air is 5% of air output.

3. Output air excess pressure ≥200Pa

4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one. 


Main Accessories