Combine freeze-drying with further rotary wheel dehumidify, Export dry air which is constant temperature and humidity. (Dry air by refrigeration dehumidifies and rotary wheel dehumidify, control temperature and humidity constantly.) It is suitable for process which have requirement for humidity and temperature.
Character:
1.Consist |
Consist of the fresh air filter, fresh air surface cooler, return air filter, former surface cooler,
and super silicone rotor section, tempering section and regeneration parts.
|
2.Regeneration |
Regeneration heating by stainless steel tube electric heater or by copper tube aluminum fin steam heater.
|
3.Structure |
Efficient centrifugal fans, high-strength structural framework, high-pressure foam double-sided enclosure, anti-cold bridge treatment.
|
4.Control |
PLC control, electric multi-protection, operation safety, stable and reliable.
|
Model Example
ZLB-D-1000
ZLB: low humidity dehumidifier units basic code
D: Rotary regeneration type. D for Electricity, Z for Steam.
1000: Process airflow m3/h
Main Parameters of ZLB Series Low Humidity Dehumidifier
Main Parameters / Model
|
ZLB-1000
|
ZLB-5000
|
ZLB-10000
|
Process Air
|
Airflow m³/h
|
1000
|
5000
|
10000
|
Fan Power kW
|
1.1
|
4.0
|
7.5
|
Regeneration Air
|
Airflow m³/h
|
340
|
1650
|
3450
|
Fan Power kW
|
0.25
|
1.5
|
3.0
|
Regeneration Mode
|
Electrical Heating Power kW
|
8.4
|
36
|
84
|
Steam Consumption kg/h
|
14
|
60
|
140
|
Outlet Air
|
Temperature °C
|
22±2
|
Relative Humidity %
|
≤20
|
Drive Motor Power kW
|
0.06
|
0.12
|
0.16
|
Installed Power
|
Electrical Heating kW
|
9.81
|
41.62
|
94.68
|
Steam Heating kW
|
1.41
|
5.62
|
10.68
|
Overall Dimensions
|
Length mm
|
5000
|
5700
|
6000
|
Width mm
|
800
|
1230
|
1630
|
Height mm
|
1800
|
2300
|
2650
|
Weight kg
|
1200
|
1800
|
2400
|
Supporting System Refrigerating Capacity kW
|
10.0
|
49.9
|
99.8
|
Frozen Water Consumption t/h
|
1.7
|
8.6
|
17.2
|
Note:
1. Parameter of fresh air: 35°C, 80%
2. The ratio of fresh air is 5% of air output.
3. Output air excess pressure ≥200Pa
4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one.
Main Accessories

Rotor