ZLB Series Soft Gelatine Capsule Industry Rotor Dehumidifier
Place of Origin Zhejiang, China (Mainland)
Brand Name Peritek
Model Number ZLB
Color White
 ZLB Series Low Humidity Dehumidifier Units(Pharmaceutical ,Chemical and Food Industry)

Combine freeze-drying with further rotary wheel dehumidify, Export dry air which is constant temperature and humidity. (Dry air by refrigeration dehumidifies and rotary wheel dehumidify, control temperature and humidity constantly.) It is suitable for process which have requirement for humidity and temperature.

 

Character

1)        Intake air filter, silica gel desiccant wheel, double cold-water heat exchanger;

2)        Chain drive;

3)        Electric heating by stainless steel tube, or by copper tube aluminum fin;

4)        Efficient centrifugal fans, aluminum alloy frame, high pressure polyurethane and double foam layer cabinet, anti-cold bridge, electric multi-protection operation;

5)        Reliable PLC control system.

 

Model Example

ZLB-D-5000

ZLB: low humidity dehumidifier units basic code 

D: Rotary regeneration type. D for Electricity, Z for Steam.

5000: Process airflow m3/h

 

Main Parameters of ZLB Series Low Humidity Dehumidifier

Main Parameters /  Model 

ZLB-1000

ZLB-5000

ZLB-10000

Process Air

Airflow m³/h

1000

 5000

10000

Fan Power kW

1.1

4.0

7.5

Regeneration Air

Airflow m³/h

340

1650

3450

Fan Power kW

0.25

1.5

3.0

Regeneration Mode

Electrical Heating Power kW

8.4

36

84

Steam Consumption kg/h

14

60

140

Outlet Air

Temperature °C

22±2

Relative Humidity %

 ≤20

Drive Motor Power kW

0.06

0.12

0.16

Installed Power

Electrical Heating  kW

9.81

41.62

94.68

Steam Heating kW

1.41

5.62

10.68

Overall Dimensions

Length  mm

5000

5700

6000

Width  mm

800

1230

1630

Height  mm

1800

2300

2650

Weight kg

1200

1800

2400

Supporting System Refrigerating Capacity kW

10.0

49.9

99.8

Frozen Water Consumption t/h

1.7

8.6

17.2

Note

1. Parameter of fresh air: 35°C, 80%

2. The ratio of fresh air is 5% of air output.

3. Output air excess pressure ≥200Pa

4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one. 

 

Main Accessories